GENIUS 250

Low Temperature Air Cooled Chiller

Model No: GENIUS 250
Cooling Capacity: Rated at 500 Watts @ -40°C, 1900 W @ -20°C, de-rate 17% for 50Hz

NOTE: Cooling capacity is pump dependent. Meaning some pump options will decrease cooling capacity.

Temperature Range: -40°C to 30°C
Fluid Type: Water/glycol, 40/60% mixture by volume, mixture is temperature dependent, call for other applicable fluid


Unit Consists of the Following

Condenser:

  • Air-cooled, aluminum fin and copper tube, 840 Max CFM (Water cooled condenser available)

Refrigeration Circuit:

  • One (1) Hermetic compressor rated at 2.5 H.P. utilizing CFC free refrigerant
  • High and low refrigerant pressure protection, compressor control module.
  • Hot gas bypass for tight temperature control, heating capacity & extended compressor life
  • Filter drier and refrigerant sight glass, hard brazed connections
  • Highest efficiency brazed plate evaporator

Circulating Pump:

  • 2 GPM @ up to 99 PSIG on 60Hz, with 0.5 HP motor upgrade for low viscosity fluid @ -40C
  • Fluid bypass/pressure regulating valve externally adjustable
  • Liquid filled pressure gauge in PSIG/kPA 100 PSIG

Reservoir Capacity:

  • Seamless 2 gallon Polyethylene
  • Insulation included

Controller:

  • Off the shelf, no proprietary boards, field replaceable
  • Modular electronic solid state
  • Flash/Non-Volatile Memory
  • Full featured PID controller with easy Auto-tuning
  • Dual digital readout for set point and process temperature
  • +/-0.1oC on static load control
  • User adjustable temperature alarms
  • Cooling, heating, alarm, remote output indicators
  • DB9F, USB, LAN remote port, select type

System Readouts Diagnostic Display E

  • Touch Screen Control
  • Level Low / Low Flow / Temperature Alarm
  • Remote start / stop -Auto restart when in REMOTE mode on power loss
  • Coolant over & under temperature warning light & unit shutdown
  • Level low switch and warning light and unit shutdown
  • Low flow switch, warning light and unit shutdown
  • Remote On/Off via control closure, 24 VDC present
  • PLC retains program up to 20 years while unpowered
  • Remote connector specification: Pins 1 & 9, NC – dry contact, chiller fault status. Pins 3 & 7, 24
  • VDC+ (pin 3), Common (pin 7), close for remote start
  • Remote Mode Memory, unit retains status, restarts on power loss

Electrical: (For GENIUS 250)

  • Voltage/Phase/Frequency: 200-230V / 1 / 50/60Hz, Code C2, other phase and voltage options available.
  • Circuit Breaker/Amperage draw: 32A / 20.3FLA
  • Enclosure Type: NEMA 1
  • Cord type or Plug type: 15’ standard / No plug due to wide variance
  • Thermal protection of pump and compressor motors via motor overload device
  • UL, CE, IEC, & RoHS listed electrical components and practices

Frame:

  • Dimensions: 24.125″W x 31.125″D x 36″H on Casters
  • Four locking casters with non-marring wheels

Utility Requirements 

Fittings:

  • Supply & Return:1/2” SS FPT
  • Facility Cooling Water Supply & Return: NA
  • Drain:1⁄2”FPT with Ball valve
  • Pressure Relief: NA

Facility Cooling Water:

  • NA. Water cooled versions available